Veritas Appliance Safety and Maintenance Guide
Installing hardware into a rack
These guidelines provide information for installing hardware into an equipment rack.
The following devices are EIA-310 compliant.
Veritas Access 3340 Appliance
Veritas Access 3350 Appliance
Veritas Access 3350 Appliance
Veritas Access 3360 Appliance
NetBackup 5230 Appliance
NetBackup 5240 Appliance
NetBackup 5330 Appliance
NetBackup 5330 Primary Storage Shelf
NetBackup 5330 Expansion Storage Shelf
Veritas 5150 Appliance
Veritas 5250 Appliance
Veritas 5260 Appliance
Veritas 5340 Appliance
Veritas 5350 Appliance
Veritas 5360 Appliance
Veritas 2U12 49TB Storage Shelf
Veritas 2U12 65TiB/72TB Storage Shelf
Veritas 3U16 24TB Storage Shelf
Veritas 3U16 36TB Storage Shelf
Veritas 5U84 Primary Storage Shelf
Veritas 5U84 Expansion Storage Shelf
Ensure that you comply with the following rack installation guidelines:
Anchor the equipment rack
The equipment rack must be anchored to an unmovable support to prevent it from falling over. The rack can fall when one or more units are extended in front of the rack on the slides. You must also consider the weight of any other device that is installed in the rack. A crush hazard exists and can cause serious injury should the rack tilt forward.
Check temperature
When the devices are installed in an equipment rack, the temperature must be in the range of 5C (41F) to 40C (104F). Extreme fluctuations in temperature can cause a variety of problems for the appliance.
Check ventilation
The equipment rack must provide sufficient airflow to the front of the devices to maintain proper cooling. The rack must also include ventilation sufficient to exhaust a maximum of 2550 BTUs (British Thermal Units) per hour for the appliance. The rack that is selected and the ventilation that is provided must be suitable to the environment in which the equipment is used.
Main AC power must be accessible
The AC power cord(s) is considered the main disconnect for the device and must be readily accessible when installed. If the individual power cord(s) are not readily accessible for disconnection, you must install an AC power disconnect for the entire rack unit. This main disconnect must be readily accessible, and it must be labeled as controlling power to the entire rack unit.
Grounding the rack installation
To avoid the potential for an electrical shock hazard, you must include a third wire safety ground conductor with the rack installation. The rack itself must have a proper grounding when device power cords are plugged into the AC outlet of the rack. The devices must be plugged into a properly grounded AC outlet.
Overcurrent protection
The power supplies contain internal overcurrent protection. If power draw increases, the power supplies shutdown. Hardware monitoring utilities such as the NetBackup Appliance Web Console show alerts that indicate problems in the power supply.
Access 3340/3350/3360 Appliance
110 VAC - 220 VAC at 2.6 A
NetBackup 5230/5330 Appliance (depending on power source input current):
100 VAC to 127 VAC @ 9.2 A
200 VAC to 240 VAC @ 4.4 A
NetBackup 5330 Primary Storage Shelf / Expansion Storage Shelf:
200 VAC @7.56 A to 240 VAC @ 6.3 A
NetBackup 5240 Appliance (depending on power source input current):
110 VAC @ 5.05 A
220 VAC @ 2.53 A
Veritas 5150 Appliance:
110 VAC @ 3.64 A
220 VAC @ 1.82 A
Veritas 5250 Appliance:
110 VAC @ 6.2 A
220 VAC @ 3.2 A
Veritas 5340 Appliance:
110 VAC - 220 VAC @ 3.1 A
Veritas 5350 Appliance:
110 VAC - 220 VAC @ 3.1 A
Veritas 2U12 49TB Storage Shelf:
110 VAC @ 5.86 A
220 VAC @ 2.93 A
Veritas 2U12 65TiB/72TB Storage Shelf:
110 VAC @ 5.86 A
220 VAC @ 2.93 A
Veritas 3U16 24TB Storage Shelf / Veritas 3U16 36TB Storage Shelf:
100 VAC to 127 VAC
200 VAC to 240 VAC
Veritas 5U84 Primary Storage Shelf / Expansion Storage Shelf:
200 VAC @ 6.67 A
Veritas Storage Shelf:
100 VAC to 127 VAC
200 VAC to 240 VAC
Signal cables must be separately bundled from the strong-current cables and high-voltage cables at a spacing of at least 30 mm.